Power Utility Test & Measure Equipments
Test & Measure ...
 

INSULATING OIL TESTERS: UC SERIES FULLY AUTOMATIC

 
  • Easy operation-Fully automatic test cycle along with average BDV display.
  • Ergonomic design, completely user friendly-just 28 kg in weight.
  • Pre settable – Number of tests, Stew time and stir time
  • 25 mm 3 digit LED display for kV and time. 1 digit display for number of tests.
  • Keep position.
  • Output voltages to 60 and 80 kV.
  • Tests to: IS 6792, IEC 156, JIS C2101, BS 5874, VDE 0370, GB-86 etc
  • Indicators for – Power on, HV rise, HV fall, Stir and Static (Stew).
  • Built in printer.
  • Countdown of stew time and stir time.
  • Zero start safety and test chamber access interlock.
 
Introduction:
Insulating oil being an efficient cooling medium with high dielectric strength has been a recognized insulating medium in electrical equipments. Degradation of oil takes place due to acids, oxidation, sludge, gas and water absorption. A dielectric strength test shows the changes caused in oil due to these processes. ‘UDEY’ Series UC insulating oil testers are fully automatic microcontroller based testers completely self contained with built in printer. ‘UDEY’ insulating oil testers are the industry standard for over 47 years.

System Description:

The system is fully automatic and carries out tests according to the set parameters like ‘Number of tests, stew time and stir time’ set in advance. Various status indicators like Power on, HV rise, HV fall, Stir and static are provided. Countdown of stew time and stir time is displayed. Audio beep is given after the test is complete and the results can be printed on built- in printer. Further the readings can be recalled after the test.
 
Technical Specifications:

Input Supply
220 Volts AC, 50 Hz, single phase.
Test Voltage Model: UC-80 (80 kV.)      Model: UC-60 (60 kV.)
Rate of rise of voltage 2 kV per second ± 10%.
kV Indication Three digit, 1” LED display.
Test number indication One digit, 1” LED display.
Status Indicators Led indicators for ‘Power on’, ‘HV rise’,’ HV fall’, ‘stir’ and ‘static’.
Test functions Reset, Run, Keep, Alarm, Print and Display.
Number of Tests Settable from 1 to 9 tests.
Stirring time Settable from 0 to 99 seconds.
Stewing time Settable from 0 to 9 minutes 59 seconds.
Electrodes 36 mm mushroom
Gap gauge 2.5 mm.
Printer Built in printer for printing results.
Construction In light weight cabinet with cover and lifting handles.
Temperature range 5 to 40º C.
Relative humidity
< 90% RH
Dimensions and weight 420 x 325 x 300 mm. Net 28 kg.
Accessories 1) Test cell with electrodes, gauge and spin bar.
2) Mains cord.
3) Paper roll.
4) Spare fuses.
5) Operating manual.