The 'UDEY SC-10' secondary current injector is a tester with
rating of 100 Amp -2 kVA with built in timer. This will test instantaneous
relays, IDMT relays, directional relays, molded circuit breakers
and meters. Current or voltage at each of the four main sets of
a.c. terminals is continuously variable.
The outputs are:
-
0 to 100 A a.c. or 0 to 20 V a.c.
-
0 to 50 A a.c. or 0 to 40 V a.c.
-
0 to 20 A a.c. or 0 to 100 V a.c.
-
0 to 5 A a.c. or 0 to 240 V a.c.
Output current flowing thru the common terminal is measured to
a resolution of 10 mA. Also a variable output of 0 to 240 V d.c.
and an independently controlled output of 0 to 240 V a.c. is available
to allow testing of directional relays. Two digital displays are
used. A 3½ digit display to show the output current or
voltage (by means of meter range selector switch). The other is
a four digit display to show readings of the timer. A 'SET/TEST'
switch is provided so that the appropriate current can be set
up before the test is actually carried out, and to avoid damage
to relay coils by disconnecting the test current after the device
has operated. The timer has six custom operating modes: 'NO',
'NC', 'CUR' 'RUNBACK NO', 'RUNBACK NC' and 'MANUAL'. These enable
the function of a protective relay to be fully tested. Separate
terminals are provided for connecting to the tripping contacts
of the relay. The timer has 'RESET' pushbutton and two manual
pushbuttons.
|