Surge Arrestor Leakage Current Analyzer
Model : Surge Arrestor Leakage Current Analyzer
ASA-603
Introduction:
Udey ASA-603 is used to measure leakage current of Metal Oxide Arrestor (MOA). The main test is resistive current to find out ageing or inside damp of MOA. ASA-603 can be used at site as well as Laboratory test.
Description:
ASA-603 conducts test in two methods:
1. To test resistive current with a reference voltage, normally from secondary of potential transformer (PT). This method is quite common and offers best accuracy.
2. To test resistive current with a reference electrical field. A metal plate is mounted at the base of the MOA of Ø B to induct the electrical field which contains the phase information of the BUS voltage. This method is simple and offers good accuracy.
ASA-603 is easy to operate, accurate readings. The tester works on rechargeable battery, calendar, clock, printer, memory for 100 groups of test data and RS 232 port to transfer stored data to computer.
Machine Feature
1. Makes test easy and quickly
2. All calculations are based on known standard theory, which is widely accepted.
3. Fully digital processing through embedded microprocessor enables high accuracy, reliability and stability.
4. Two isolated channels to input the leakage current and reference signal which eliminates the magnetic interference.
5. Big LCD with backlit and four key operation menu.
Range of leakage current | 0-10mA (RMS), 50 Hz/60 Hz. |
---|---|
Accuracy of leakage current | ± (reading x 5% + 5 uA) |
Accuracy of fundamental resistance current (PT mode/ No interference) | ± (reading x 5% + 5 uA) |
Accuracy of current harmonic | ± (reading x 10% + 10 uA) |
Input impedance of leakage current | ≤2Ω |
Range of reference voltage | 25-250V (RMS), 50 Hz/60 Hz. |
Accuracy of reference voltage | ± (reading x 5% + 0.5 V) |
Accuracy of voltage harmonic | ± (reading x 10%) |
Input impedance of leakage current | ≥300K Ω |
Range of electrical field | 30kV/m – 300kV/m. |
Accuracy of electrical field | ± (reading x 10%) |
Accuracy of electrical field harmonic | ± (reading x 10%) |
Battery duration | 6 hrs continuous at full charge. |
Charging input | 100-250V, 50 Hz/60Hz. |
Charging time | 6 hrs approximately. |
Operating conditions | 0-60 Deg.C., |
Storage temperature | -20 to 60 Deg.C. |
Relative Humidity | <90% non-condensing |
Dimensions | 35 cm (L) x 28 cm (W) x 18 cm (H) |
Weight | 5 kg ( tester) ; 4 kgs (Cable Case) |
Standard Accessory
- Cable to Uref socket small clamp – 1 no
- Cable to Ix socket big clamp – 1 no
- Extended Cable for Uref of 100 metres – 1 no
- Extended Cable for Ix of 20 metres – 1 no
- Inductive Metal board – 1 no
- RS 232 cable of 5 metres – 1 no
- USB cable – 1 no
- Charger – 1 no
- Ground wire of 8 metres – 1 no
- Paper Roll – 1 no
- Software Installation CD – 1 no
- + Feature
Machine Feature
1. Makes test easy and quickly
2. All calculations are based on known standard theory, which is widely accepted.
3. Fully digital processing through embedded microprocessor enables high accuracy, reliability and stability.
4. Two isolated channels to input the leakage current and reference signal which eliminates the magnetic interference.
5. Big LCD with backlit and four key operation menu.
- + Technical Specification
Range of leakage current 0-10mA (RMS), 50 Hz/60 Hz. Accuracy of leakage current ± (reading x 5% + 5 uA) Accuracy of fundamental resistance current (PT mode/ No interference) ± (reading x 5% + 5 uA) Accuracy of current harmonic ± (reading x 10% + 10 uA) Input impedance of leakage current ≤2Ω Range of reference voltage 25-250V (RMS), 50 Hz/60 Hz. Accuracy of reference voltage ± (reading x 5% + 0.5 V) Accuracy of voltage harmonic ± (reading x 10%) Input impedance of leakage current ≥300K Ω Range of electrical field 30kV/m – 300kV/m. Accuracy of electrical field ± (reading x 10%) Accuracy of electrical field harmonic ± (reading x 10%) Battery duration 6 hrs continuous at full charge. Charging input 100-250V, 50 Hz/60Hz. Charging time 6 hrs approximately. Operating conditions 0-60 Deg.C., Storage temperature -20 to 60 Deg.C. Relative Humidity <90% non-condensing Dimensions 35 cm (L) x 28 cm (W) x 18 cm (H) Weight 5 kg ( tester) ; 4 kgs (Cable Case) - + Standard Accessory
Standard Accessory
- Cable to Uref socket small clamp – 1 no
- Cable to Ix socket big clamp – 1 no
- Extended Cable for Uref of 100 metres – 1 no
- Extended Cable for Ix of 20 metres – 1 no
- Inductive Metal board – 1 no
- RS 232 cable of 5 metres – 1 no
- USB cable – 1 no
- Charger – 1 no
- Ground wire of 8 metres – 1 no
- Paper Roll – 1 no
- Software Installation CD – 1 no